{"id":115,"date":"2015-04-21T11:01:27","date_gmt":"2015-04-21T16:01:27","guid":{"rendered":"\/\/blogs.baersupply.com\/?p=115"},"modified":"2025-12-18T15:45:23","modified_gmt":"2025-12-18T21:45:23","slug":"attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety","status":"publish","type":"post","link":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety","title":{"rendered":"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety"},"content":{"rendered":"<p>Underwriters Laboratories (UL) has announced a revision to standard UL 943 that will take effect on June 29, 2015. This revision requires that all UL certified Class A residential and commercial grade wallbox mounted GFCI have:<\/p>\n<ol>\n<li>An auto-monitoring function that will allow for periodic automatic testing (self-test) of the GFCI device and its ability to respond to a ground fault. If a problem is detected the GFCI will disconnect power to anything connected to it or indicate that there is a problem using visual or audible means.<\/li>\n<li>Provisions to ensure that receptacle type GFCIs that contain separate line and load terminals, and that is powered through its load terminals, shall not reset and supply power to its receptacle face or line terminals if miswired. This applies both during its initial installation and after reinstallation following a correctly wired installation. If the device is provided with special instructions for removal and reinstallation, the instructions shall be followed during testing.<\/li>\n<\/ol>\n<p>Visit the Leviton website at <a href=\"\/\/www.leviton.com\/OA_HTML\/SectionDisplay.jsp?section=66915&#038;minisite=10251\" class=\"bodyLink\">\/\/www.leviton.com\/OA_HTML\/SectionDisplay.jsp?section=66915&#038;minisite=10251<\/a> for more information about these new standards.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Underwriters Laboratories (UL) has announced a revision to standard UL 943 that will take effect&hellip;<\/p>\n","protected":false},"author":2,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[366],"tags":[91,95,94,63,90,89,88,92,93],"class_list":["post-115","post","type-post","status-publish","format-standard","hentry","category-informational","tag-bath","tag-electrical-2","tag-gfci","tag-improvements-2","tag-kitchen","tag-remodeler","tag-safety-2","tag-ul","tag-underwriters"],"aioseo_notices":[],"aioseo_head":"\n\t\t<!-- All in One SEO Pro 5.0.3 - aioseo.com -->\n\t<meta name=\"description\" content=\"Underwriters Laboratories (UL) has announced a revision to standard UL 943 that will take effect on June 29, 2015. This revision requires that all UL certified Class A residential and commercial grade wallbox mounted GFCI have: An auto-monitoring function that will allow for periodic automatic testing (self-test) of the GFCI device and its ability to\" \/>\n\t<meta name=\"robots\" content=\"max-image-preview:large\" \/>\n\t<meta name=\"author\" content=\"Kevin Wojdak\"\/>\n\t<link rel=\"canonical\" href=\"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety\" \/>\n\t\t<meta name=\"generator\" content=\"All in One SEO Pro (AIOSEO) 5.0.3\" \/>\n\t\t<meta property=\"og:locale\" content=\"en_US\" \/>\n\t\t<meta property=\"og:site_name\" content=\"The W\u00fcrth Baer Facts Blog - What&#039;s New at W\u00fcrth Baer Supply Company\" \/>\n\t\t<meta property=\"og:type\" content=\"article\" \/>\n\t\t<meta property=\"og:title\" content=\"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety - The W\u00fcrth Baer Facts Blog\" \/>\n\t\t<meta property=\"og:description\" content=\"Underwriters Laboratories (UL) has announced a revision to standard UL 943 that will take effect on June 29, 2015. This revision requires that all UL certified Class A residential and commercial grade wallbox mounted GFCI have: An auto-monitoring function that will allow for periodic automatic testing (self-test) of the GFCI device and its ability to\" \/>\n\t\t<meta property=\"og:url\" content=\"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety\" \/>\n\t\t<meta property=\"og:image\" content=\"https:\/\/wurthbaersupply.com\/blog\/wp-content\/uploads\/2025\/11\/Wurth_Logo-scaled.png\" \/>\n\t\t<meta property=\"og:image:secure_url\" content=\"https:\/\/wurthbaersupply.com\/blog\/wp-content\/uploads\/2025\/11\/Wurth_Logo-scaled.png\" \/>\n\t\t<meta property=\"article:published_time\" content=\"2015-04-21T16:01:27+00:00\" \/>\n\t\t<meta property=\"article:modified_time\" content=\"2025-12-18T21:45:23+00:00\" \/>\n\t\t<meta property=\"article:publisher\" content=\"https:\/\/www.facebook.com\/wurthbaersupply\" \/>\n\t\t<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n\t\t<meta name=\"twitter:site\" content=\"@WurthBaerSupply\" \/>\n\t\t<meta name=\"twitter:title\" content=\"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety - The W\u00fcrth Baer Facts Blog\" \/>\n\t\t<meta name=\"twitter:description\" content=\"Underwriters Laboratories (UL) has announced a revision to standard UL 943 that will take effect on June 29, 2015. This revision requires that all UL certified Class A residential and commercial grade wallbox mounted GFCI have: An auto-monitoring function that will allow for periodic automatic testing (self-test) of the GFCI device and its ability to\" \/>\n\t\t<meta name=\"twitter:creator\" content=\"@WurthBaerSupply\" \/>\n\t\t<meta name=\"twitter:image\" content=\"https:\/\/wurthbaersupply.com\/blog\/wp-content\/uploads\/2025\/11\/Wurth_Logo-scaled.png\" \/>\n\t\t<script type=\"application\/ld+json\" class=\"aioseo-schema\">\n\t\t\t{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"BlogPosting\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#blogposting\",\"name\":\"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety - The W\\u00fcrth Baer Facts Blog\",\"headline\":\"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety\",\"author\":{\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/author\\\/wojdakk#author\"},\"publisher\":{\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/#organization\"},\"image\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/wp-content\\\/uploads\\\/2025\\\/11\\\/Wurth_Logo-scaled.png\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/#articleImage\",\"width\":2560,\"height\":550,\"caption\":\"W\\u00fcrth Logo\"},\"datePublished\":\"2015-04-21T11:01:27-06:00\",\"dateModified\":\"2025-12-18T15:45:23-06:00\",\"inLanguage\":\"en-US\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#webpage\"},\"isPartOf\":{\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#webpage\"},\"articleSection\":\"Informational, bath, electrical, GFCI, improvements, kitchen, remodeler, safety, UL, Underwriters\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#breadcrumblist\",\"itemListElement\":[{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/#listItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/category\\\/informational#listItem\",\"name\":\"Informational\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/category\\\/informational#listItem\",\"position\":2,\"name\":\"Informational\",\"item\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/category\\\/informational\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#listItem\",\"name\":\"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety\"},\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/#listItem\",\"name\":\"Home\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#listItem\",\"position\":3,\"name\":\"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety\",\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/category\\\/informational#listItem\",\"name\":\"Informational\"}}]},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/#organization\",\"name\":\"W\\u00fcrth Baer Supply Company\",\"description\":\"A Specialty Wholesale Distributor to the Woodworking Industry\",\"url\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/\",\"telephone\":\"+18002892237\",\"logo\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/wp-content\\\/uploads\\\/2025\\\/11\\\/Wurth_Logo-scaled.png\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety\\\/#organizationLogo\",\"width\":2560,\"height\":550,\"caption\":\"W\\u00fcrth Logo\"},\"image\":{\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety\\\/#organizationLogo\"},\"sameAs\":[\"https:\\\/\\\/www.facebook.com\\\/wurthbaersupply\",\"https:\\\/\\\/www.twitter.com\\\/WurthBaerSupply\",\"https:\\\/\\\/www.instagram.com\\\/wurthbaer\\\/\",\"https:\\\/\\\/www.tiktok.com\\\/@wurthbaersupplycompany\",\"https:\\\/\\\/pinterest.com\\\/wurthbaersupply\\\/\",\"https:\\\/\\\/www.youtube.com\\\/channel\\\/UCWgXJp8XZ1hCkTe7AvrMJVQ\",\"https:\\\/\\\/www.linkedin.com\\\/company\\\/baer-supply-company\\\/\"]},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/author\\\/wojdakk#author\",\"url\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/author\\\/wojdakk\",\"name\":\"Kevin Wojdak\",\"image\":{\"@type\":\"ImageObject\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#authorImage\",\"url\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/wp-content\\\/uploads\\\/2026\\\/03\\\/Wojdak_Kevin_square.png\",\"width\":1700,\"height\":1700},\"jobTitle\":\"E-Commerce Manager\"},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#webpage\",\"url\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety\",\"name\":\"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety - The W\\u00fcrth Baer Facts Blog\",\"description\":\"Underwriters Laboratories (UL) has announced a revision to standard UL 943 that will take effect on June 29, 2015. This revision requires that all UL certified Class A residential and commercial grade wallbox mounted GFCI have: An auto-monitoring function that will allow for periodic automatic testing (self-test) of the GFCI device and its ability to\",\"inLanguage\":\"en-US\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/#website\"},\"breadcrumb\":{\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/2015\\\/04\\\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#breadcrumblist\"},\"author\":{\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/author\\\/wojdakk#author\"},\"creator\":{\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/author\\\/wojdakk#author\"},\"datePublished\":\"2015-04-21T11:01:27-06:00\",\"dateModified\":\"2025-12-18T15:45:23-06:00\"},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/#website\",\"url\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/\",\"name\":\"The W\\u00fcrth Baer Facts Blog\",\"description\":\"What's New at W\\u00fcrth Baer Supply Company\",\"inLanguage\":\"en-US\",\"publisher\":{\"@id\":\"https:\\\/\\\/wurthbaersupply.com\\\/blog\\\/#organization\"}}]}\n\t\t<\/script>\n\t\t<!-- All in One SEO Pro -->\r\n\t\t<title>Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety - The W\u00fcrth Baer Facts Blog<\/title>\n\n","aioseo_head_json":{"title":"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety - The W\u00fcrth Baer Facts Blog","description":"Underwriters Laboratories (UL) has announced a revision to standard UL 943 that will take effect on June 29, 2015. This revision requires that all UL certified Class A residential and commercial grade wallbox mounted GFCI have: An auto-monitoring function that will allow for periodic automatic testing (self-test) of the GFCI device and its ability to","canonical_url":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety","robots":"max-image-preview:large","keywords":"","webmasterTools":{"miscellaneous":""},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"BlogPosting","@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#blogposting","name":"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety - The W\u00fcrth Baer Facts Blog","headline":"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety","author":{"@id":"https:\/\/wurthbaersupply.com\/blog\/author\/wojdakk#author"},"publisher":{"@id":"https:\/\/wurthbaersupply.com\/blog\/#organization"},"image":{"@type":"ImageObject","url":"https:\/\/wurthbaersupply.com\/blog\/wp-content\/uploads\/2025\/11\/Wurth_Logo-scaled.png","@id":"https:\/\/wurthbaersupply.com\/blog\/#articleImage","width":2560,"height":550,"caption":"W\u00fcrth Logo"},"datePublished":"2015-04-21T11:01:27-06:00","dateModified":"2025-12-18T15:45:23-06:00","inLanguage":"en-US","mainEntityOfPage":{"@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#webpage"},"isPartOf":{"@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#webpage"},"articleSection":"Informational, bath, electrical, GFCI, improvements, kitchen, remodeler, safety, UL, Underwriters"},{"@type":"BreadcrumbList","@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#breadcrumblist","itemListElement":[{"@type":"ListItem","@id":"https:\/\/wurthbaersupply.com\/blog\/#listItem","position":1,"name":"Home","item":"https:\/\/wurthbaersupply.com\/blog\/","nextItem":{"@type":"ListItem","@id":"https:\/\/wurthbaersupply.com\/blog\/category\/informational#listItem","name":"Informational"}},{"@type":"ListItem","@id":"https:\/\/wurthbaersupply.com\/blog\/category\/informational#listItem","position":2,"name":"Informational","item":"https:\/\/wurthbaersupply.com\/blog\/category\/informational","nextItem":{"@type":"ListItem","@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#listItem","name":"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety"},"previousItem":{"@type":"ListItem","@id":"https:\/\/wurthbaersupply.com\/blog\/#listItem","name":"Home"}},{"@type":"ListItem","@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#listItem","position":3,"name":"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety","previousItem":{"@type":"ListItem","@id":"https:\/\/wurthbaersupply.com\/blog\/category\/informational#listItem","name":"Informational"}}]},{"@type":"Organization","@id":"https:\/\/wurthbaersupply.com\/blog\/#organization","name":"W\u00fcrth Baer Supply Company","description":"A Specialty Wholesale Distributor to the Woodworking Industry","url":"https:\/\/wurthbaersupply.com\/blog\/","telephone":"+18002892237","logo":{"@type":"ImageObject","url":"https:\/\/wurthbaersupply.com\/blog\/wp-content\/uploads\/2025\/11\/Wurth_Logo-scaled.png","@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety\/#organizationLogo","width":2560,"height":550,"caption":"W\u00fcrth Logo"},"image":{"@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety\/#organizationLogo"},"sameAs":["https:\/\/www.facebook.com\/wurthbaersupply","https:\/\/www.twitter.com\/WurthBaerSupply","https:\/\/www.instagram.com\/wurthbaer\/","https:\/\/www.tiktok.com\/@wurthbaersupplycompany","https:\/\/pinterest.com\/wurthbaersupply\/","https:\/\/www.youtube.com\/channel\/UCWgXJp8XZ1hCkTe7AvrMJVQ","https:\/\/www.linkedin.com\/company\/baer-supply-company\/"]},{"@type":"Person","@id":"https:\/\/wurthbaersupply.com\/blog\/author\/wojdakk#author","url":"https:\/\/wurthbaersupply.com\/blog\/author\/wojdakk","name":"Kevin Wojdak","image":{"@type":"ImageObject","@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#authorImage","url":"https:\/\/wurthbaersupply.com\/blog\/wp-content\/uploads\/2026\/03\/Wojdak_Kevin_square.png","width":1700,"height":1700},"jobTitle":"E-Commerce Manager"},{"@type":"WebPage","@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#webpage","url":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety","name":"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety - The W\u00fcrth Baer Facts Blog","description":"Underwriters Laboratories (UL) has announced a revision to standard UL 943 that will take effect on June 29, 2015. This revision requires that all UL certified Class A residential and commercial grade wallbox mounted GFCI have: An auto-monitoring function that will allow for periodic automatic testing (self-test) of the GFCI device and its ability to","inLanguage":"en-US","isPartOf":{"@id":"https:\/\/wurthbaersupply.com\/blog\/#website"},"breadcrumb":{"@id":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety#breadcrumblist"},"author":{"@id":"https:\/\/wurthbaersupply.com\/blog\/author\/wojdakk#author"},"creator":{"@id":"https:\/\/wurthbaersupply.com\/blog\/author\/wojdakk#author"},"datePublished":"2015-04-21T11:01:27-06:00","dateModified":"2025-12-18T15:45:23-06:00"},{"@type":"WebSite","@id":"https:\/\/wurthbaersupply.com\/blog\/#website","url":"https:\/\/wurthbaersupply.com\/blog\/","name":"The W\u00fcrth Baer Facts Blog","description":"What's New at W\u00fcrth Baer Supply Company","inLanguage":"en-US","publisher":{"@id":"https:\/\/wurthbaersupply.com\/blog\/#organization"}}]},"og:locale":"en_US","og:site_name":"The W\u00fcrth Baer Facts Blog - What's New at W\u00fcrth Baer Supply Company","og:type":"article","og:title":"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety - The W\u00fcrth Baer Facts Blog","og:description":"Underwriters Laboratories (UL) has announced a revision to standard UL 943 that will take effect on June 29, 2015. This revision requires that all UL certified Class A residential and commercial grade wallbox mounted GFCI have: An auto-monitoring function that will allow for periodic automatic testing (self-test) of the GFCI device and its ability to","og:url":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety","og:image":"https:\/\/wurthbaersupply.com\/blog\/wp-content\/uploads\/2025\/11\/Wurth_Logo-scaled.png","og:image:secure_url":"https:\/\/wurthbaersupply.com\/blog\/wp-content\/uploads\/2025\/11\/Wurth_Logo-scaled.png","article:published_time":"2015-04-21T16:01:27+00:00","article:modified_time":"2025-12-18T21:45:23+00:00","article:publisher":"https:\/\/www.facebook.com\/wurthbaersupply","twitter:card":"summary_large_image","twitter:site":"@WurthBaerSupply","twitter:title":"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety - The W\u00fcrth Baer Facts Blog","twitter:description":"Underwriters Laboratories (UL) has announced a revision to standard UL 943 that will take effect on June 29, 2015. This revision requires that all UL certified Class A residential and commercial grade wallbox mounted GFCI have: An auto-monitoring function that will allow for periodic automatic testing (self-test) of the GFCI device and its ability to","twitter:creator":"@WurthBaerSupply","twitter:image":"https:\/\/wurthbaersupply.com\/blog\/wp-content\/uploads\/2025\/11\/Wurth_Logo-scaled.png"},"aioseo_meta_data":{"post_id":"115","title":"#post_title #separator_sa #site_title","description":"#post_excerpt","keywords":null,"keyphrases":null,"primary_term":null,"canonical_url":null,"og_title":null,"og_description":null,"og_object_type":"default","og_image_type":"default","og_image_url":null,"og_image_width":null,"og_image_height":null,"og_image_custom_url":null,"og_image_custom_fields":null,"og_video":null,"og_custom_url":null,"og_article_section":null,"og_article_tags":null,"twitter_use_og":false,"twitter_card":"default","twitter_image_type":"default","twitter_image_url":null,"twitter_image_custom_url":null,"twitter_image_custom_fields":null,"twitter_title":null,"twitter_description":null,"schema":{"blockGraphs":[],"customGraphs":[],"default":{"data":{"Article":[],"Course":[],"Dataset":[],"FAQPage":[],"Movie":[],"Person":[],"Product":[],"ProductReview":[],"Car":[],"Recipe":[],"Service":[],"SoftwareApplication":[],"WebPage":[]},"graphName":"","isEnabled":true},"graphs":[]},"schema_type":"default","schema_type_options":null,"pillar_content":false,"robots_default":true,"robots_noindex":false,"robots_noarchive":false,"robots_nosnippet":false,"robots_nofollow":false,"robots_noimageindex":false,"robots_noodp":false,"robots_notranslate":false,"robots_max_snippet":null,"robots_max_videopreview":null,"robots_max_imagepreview":"large","priority":null,"frequency":null,"local_seo":null,"seo_analyzer_scan_date":"2026-03-31 02:11:03","limit_modified_date":false,"reviewed_by":null,"ai":null,"created":"2025-11-18 21:16:09","updated":"2026-04-30 14:39:09","focus_keyword":null,"additional_keywords":null,"truseo_locale":null,"breadcrumb_settings":null},"aioseo_breadcrumb":"<div class=\"aioseo-breadcrumbs\"><span class=\"aioseo-breadcrumb\">\n\t<a href=\"https:\/\/wurthbaersupply.com\/blog\/\" title=\"Home\">Home<\/a>\n<\/span><span class=\"aioseo-breadcrumb-separator\">\u00bb<\/span><span class=\"aioseo-breadcrumb\">\n\t<a href=\"https:\/\/wurthbaersupply.com\/blog\/category\/informational\" title=\"Informational\">Informational<\/a>\n<\/span><span class=\"aioseo-breadcrumb-separator\">\u00bb<\/span><span class=\"aioseo-breadcrumb\">\n\tAttention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety\n<\/span><\/div>","aioseo_breadcrumb_json":[{"label":"Home","link":"https:\/\/wurthbaersupply.com\/blog\/"},{"label":"Informational","link":"https:\/\/wurthbaersupply.com\/blog\/category\/informational"},{"label":"Attention Kitchen and Bath Remodelers: Revised UL 943 Requirements for Added Safety","link":"https:\/\/wurthbaersupply.com\/blog\/2015\/04\/attention-kitchen-and-bath-remodelers-revised-ul-943-requirements-for-added-safety"}],"_links":{"self":[{"href":"https:\/\/wurthbaersupply.com\/blog\/wp-json\/wp\/v2\/posts\/115","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/wurthbaersupply.com\/blog\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/wurthbaersupply.com\/blog\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/wurthbaersupply.com\/blog\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/wurthbaersupply.com\/blog\/wp-json\/wp\/v2\/comments?post=115"}],"version-history":[{"count":1,"href":"https:\/\/wurthbaersupply.com\/blog\/wp-json\/wp\/v2\/posts\/115\/revisions"}],"predecessor-version":[{"id":14846,"href":"https:\/\/wurthbaersupply.com\/blog\/wp-json\/wp\/v2\/posts\/115\/revisions\/14846"}],"wp:attachment":[{"href":"https:\/\/wurthbaersupply.com\/blog\/wp-json\/wp\/v2\/media?parent=115"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/wurthbaersupply.com\/blog\/wp-json\/wp\/v2\/categories?post=115"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/wurthbaersupply.com\/blog\/wp-json\/wp\/v2\/tags?post=115"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}